Convert kVA to amps for single-phase and three-phase circuits. Free electrical calculator for electricians.
Transformers, generators, and UPS equipment are rated in kVA because that rating is set by the heat the equipment can dissipate, which depends on apparent power - not real power. To wire the equipment you need amps. Converting kVA to amps needs voltage and the system phase configuration; no power factor needed because kVA already includes it.
Single-phase amps equal kVA times 1000 divided by voltage. Three-phase divides by √3 times line-to-line voltage instead.
Single-phase: I = (kVA × 1000) ÷ V Three-phase: I = (kVA × 1000) ÷ (√3 × V_LL)
A 75 kVA, 480V to 208Y/120V three-phase transformer. Find primary and secondary FLA.
Primary: I = (75 × 1000) ÷ (1.732 × 480) = 75,000 ÷ 831.4 = 90.2 A. Secondary: I = (75 × 1000) ÷ (1.732 × 208) = 75,000 ÷ 360.3 = 208.2 A.
Primary FLA is 90.2 A, secondary FLA is 208.2 A. Use these for sizing primary and secondary conductors and OCPD per NEC 450.3.
I = (kVA × 1000) / V = (10 × 1000) / 120