Calculate voltage drop for any circuit length and wire size. Verify compliance with NEC 3% and 5% recommendations.
Voltage drop is the loss of voltage across a conductor due to its resistance. The NEC does not mandate a hard limit, but Informational Note 4 to 210.19(A) and 215.2(A)(1) recommend keeping branch circuit drop under 3% and total drop (feeder plus branch) under 5%. Drop matters because it changes how much voltage actually arrives at the load - too much drop and motors run hot, lights dim, and electronics misbehave. This calculator handles single-phase and three-phase circuits with copper or aluminum conductors.
For single-phase circuits, voltage drop equals two times the one-way length, times current, times the conductor resistance per foot, divided by 1000. Three-phase circuits use a √3 multiplier instead of 2 because the line-to-line return path is shared across phases.
Single-phase: VD = (2 × K × I × L) ÷ CM Three-phase: VD = (1.732 × K × I × L) ÷ CM (K = 12.9 copper, 21.2 aluminum; CM = circular mils; L = one-way feet)
Reference: NEC 210.19(A) Informational Note 4, 215.2(A)(1)
20-amp, 120-volt single-phase branch circuit feeding a load 150 feet from the panel using #12 copper THHN.
#12 copper has 6,530 circular mils. VD = (2 × 12.9 × 20 × 150) ÷ 6,530 = 11.85 volts. As a percent: 11.85 ÷ 120 = 9.9%.
9.9% is well over the 3% recommendation. Upsizing to #8 copper (16,510 CM) drops it to about 4.7 volts, or 3.9%, and #6 brings it under 3%.