Find the right wire size for your circuit. Accounts for ampacity, temperature derating, bundling, and voltage drop.
Wire sizing requires balancing four factors: ampacity for the load, voltage drop on the run length, temperature rating of the terminations, and any derating for ambient temperature or conductor bundling. NEC 310.16 is the starting table; 110.14(C) limits you to the 60°C or 75°C column based on terminal ratings; 310.15(B) and (C) handle derating. This calculator runs all four checks and reports the smallest conductor that satisfies them.
The required ampacity is the load current divided by the product of all derating factors. The wire chosen must have a base ampacity (from NEC 310.16) at or above that required value at the temperature column matching your terminations.
Required ampacity = load amps ÷ (temp correction factor × adjustment factor)
Reference: NEC 310.16, 310.15, 110.14(C), 240.4
A 50 A continuous load on a 75°C terminal in a raceway with 6 current-carrying conductors at 30°C ambient, copper THWN-2.
Continuous load adjustment: 50 × 1.25 = 62.5 A required. Adjustment factor for 4-6 conductors is 0.80 (Table 310.15(C)(1)). Temperature correction at 30°C is 1.00. Required ampacity = 62.5 ÷ 0.80 = 78.1 A. From NEC 310.16, 75°C copper, #4 AWG is rated 85 A.
#4 copper THWN-2 satisfies the load. Use a 70 A breaker (next standard up from 62.5 A continuous calculation) or stay at 60 A if the load actually pulls less than 50 A.
8 AWG at rated temperature
Ambient temperature factor
× 1.00Conductor fill factor
× 1.00