Size transformers and calculate overcurrent protection per NEC 450.3(B). Includes primary and secondary breaker sizing.
Transformer sizing has two halves: pick a kVA rating big enough for the connected load, then size the primary and secondary overcurrent protection per NEC 450.3(B). The OCPD rules are the trickier half because they depend on whether secondary protection is provided, and they include rounding-up allowances that the breaker sizing rules elsewhere in the code do not.
Transformer kVA equals load amps times voltage (single-phase) or √3 times line-to-line voltage times line current (three-phase), divided by 1000. Primary OCPD allows up to 125% of primary current when both primary and secondary protection are provided, or up to 250% when only primary protection is used (with conditions).
Single-phase kVA = (V × I) ÷ 1000 Three-phase kVA = (√3 × V × I) ÷ 1000 Primary FLA = kVA × 1000 ÷ V (single-phase) or kVA × 1000 ÷ (√3 × V) (three-phase)
Reference: NEC 450.3(B), Table 450.3(B)
A 45 kVA, 480V to 208Y/120V three-phase transformer with both primary and secondary protection.
Primary FLA = 45,000 ÷ (1.732 × 480) = 54.1 A. Secondary FLA = 45,000 ÷ (1.732 × 208) = 124.9 A. Primary OCPD allowed at 125% × 54.1 = 67.6 A → next standard up = 70 A. Secondary OCPD at 125% × 124.9 = 156 A → next standard up = 175 A.
Use a 70 A primary breaker and a 175 A secondary breaker. Sized the secondary feeders for at least 124.9 A (continuous adjustment if the load qualifies) and verify the panel rating downstream.
kVA = Watts / (Power Factor x 1000). Typical power factor ranges from 0.8 to 1.0.