Determine the correct breaker size for your circuit. Accounts for continuous and non-continuous loads per NEC 240.6(A).
Picking the right breaker means matching the load type to the NEC sizing rules and then snapping to a standard breaker size from NEC 240.6(A). For continuous loads (any load expected to run for three hours or more), the breaker has to be sized at 125% of the load. Non-continuous loads use 100%. Mixed loads add the two together. The result is then rounded up to the next standard breaker size.
For a circuit with both continuous and non-continuous loads, multiply the continuous portion by 1.25, add the non-continuous portion, and round up to the next standard breaker.
Breaker size ≥ (1.25 × continuous load) + (1.00 × non-continuous load), rounded up to a standard size from 240.6(A).
Reference: NEC 210.20(A), 215.3, 240.6(A), 422.10
A commercial lighting circuit pulls 16 A continuously. No non-continuous load.
16 A × 1.25 = 20 A. The next standard breaker size at or above 20 A is 20 A itself.
Use a 20 A breaker. Verify the branch circuit conductors are at least #12 copper THHN at 75°C (rated 25 A, derated as needed) so the breaker is properly protected.
Continuous loads run for 3+ hours. Per NEC, they must be derated to 125% for breaker sizing.