NEC Article 250 Practice Questions: Grounding and Bonding
The two tables every examinee must own — 250.66 and 250.122 — plus electrodes, bonding jumpers, and separately derived systems. Grounding is the most feared article; make it a strength.
What Article 250 Covers on the Exam
Article 250 is the longest article in the code and the one candidates fear most. The exam concentrates on a few high-value skills: sizing grounding electrode conductors from Table 250.66, sizing equipment grounding conductors from Table 250.122, identifying grounding electrodes (250.52), and bonding at services and separately derived systems. Master the two tables and the electrode list and Article 250 becomes free points.
Tested subtopics from Article 250
- Grounding electrode conductor sizing — Table 250.66
- Equipment grounding conductor sizing — Table 250.122
- Grounding electrode system: which electrodes qualify — 250.52 and 250.53
- Main bonding jumpers and system bonding jumpers — 250.24 and 250.30
- Bonding of metal water piping and structural steel — 250.104
Drill a different article
49 questions in our bank cite Article 250. Practice the other high-yield articles too:
How to Study Article 250
Tab Table 250.66 and Table 250.122 and drill telling them apart: 250.66 keys off the service-entrance conductor size (for grounding electrode conductors), while 250.122 keys off the overcurrent device rating (for equipment grounding conductors). Half of all Article 250 exam mistakes are using the wrong table. Also memorize the 250.66 shortcuts: a GEC to a rod electrode never needs to be larger than 6 AWG copper, and to a concrete-encased electrode never larger than 4 AWG.
Then put it under exam conditions: the free diagnostic scores you across every category and shows whether grounding and bonding is actually a weak area — or whether your study time belongs somewhere else.
Sample Questions (From Our Real Question Bank)
Here are 4 real questions from our question bank. The free diagnostic quiz has 10 more.
1. Per NEC 250.66, what is the minimum size copper grounding electrode conductor for a service with 2 AWG copper service-entrance conductors?
- A10 AWG
- B8 AWG
- C6 AWG
- D4 AWG
Show explanation
NEC Table 250.66 specifies minimum 8 AWG copper grounding electrode conductor for 2 AWG service-entrance conductors.
2. Per NEC 250.52(A)(1), a metal underground water pipe in direct contact with the earth for how many feet or more shall be used as a grounding electrode?
- A5 feet
- B8 feet
- C10 feet
- D20 feet
Show explanation
NEC 250.52(A)(1) permits metal underground water pipe as a grounding electrode when 10 feet or more is in direct earth contact.
3. Per NEC 250.30(A), a separately derived system that is a grounded system shall have which of the following?
- AA system bonding jumper
- BAn isolated ground
- CA separate grounding electrode system disconnected from the building ground
- DNo connection to the grounding electrode system
Show explanation
NEC 250.30(A) requires a grounded separately derived system to have a system bonding jumper connecting the grounded conductor to the equipment grounding conductor.
4. Per NEC 250.52(A)(2), a metal in-ground support structure shall qualify as a grounding electrode when which condition is met?
- AThe structure is over three stories tall
- BThe structure is in direct contact with the earth vertically for 10 ft (3.0 m) or more, with or without concrete encasement
- CThe structure supports electrical equipment
- DThe building has a lightning protection system
Show explanation
Per NEC 250.52(A)(2), one or more metal in-ground support structures (such as pilings, casings, or other structural metal) qualify as grounding electrodes when they are in direct contact with the earth vertically for 3.0 m (10 ft) or more, with or without concrete encasement. The phrase 'effectively grounded' does not appear in this section and is not the specified condition.
Frequently Asked Questions
What is the difference between Table 250.66 and Table 250.122?
Table 250.66 sizes the grounding electrode conductor based on the size of the service-entrance conductors. Table 250.122 sizes equipment grounding conductors based on the rating of the overcurrent device ahead of the circuit. Picking the wrong table is the most common Article 250 exam mistake.
What size grounding electrode conductor do I need for a ground rod?
Per 250.66(A), the portion of a grounding electrode conductor that connects only to a rod, pipe, or plate electrode is never required to be larger than 6 AWG copper (or 4 AWG aluminum), regardless of service size.
Which electrodes make up the grounding electrode system?
Per 250.52(A): metal underground water pipe (10 ft or more in contact with earth), metal in-ground support structure, concrete-encased electrode (Ufer), ground ring, rod and pipe electrodes, plate electrodes, and other listed electrodes. All that are present at a building must be bonded together into one system per 250.50.
Ready to Drill Every Grounding and Bonding Question?
The free diagnostic shows where you stand. A paid plan unlocks all 49 Article 250 questions — and the other 800+.
Monthly
$49/month
- 7-day free trial
- Full question bank
- Timed practice exams
- Progress tracking
- Detailed explanations
3-Month Pass
Best Value$99 one-time
$33/month - save 33%
- Everything in Monthly
- Best value for exam prep
- Study at your own pace
- One-time payment
6-Month Pass
$149 one-time
$25/month - save 49%
- Everything in Monthly
- Maximum savings
- Full exam prep cycle
- One-time payment
Take the Free Diagnostic
10 questions. No signup. Instant score, category breakdown, and NEC references for every answer.