Electrician Prep

Practice Questions: Grounding & Bonding

Real questions from our bank, each cited to the exact NEC section. Tap “Show explanation” after you answer.

NEC NEC 250.52(A)(2)Question 1

Per NEC 250.52(A)(2), a metal in-ground support structure shall qualify as a grounding electrode when which condition is met?

  • AThe structure is over three stories tall
  • BThe structure is in direct contact with the earth vertically for 10 ft (3.0 m) or more, with or without concrete encasement
  • CThe structure supports electrical equipment
  • DThe building has a lightning protection system
Show explanation

Per NEC 250.52(A)(2), one or more metal in-ground support structures (such as pilings, casings, or other structural metal) qualify as grounding electrodes when they are in direct contact with the earth vertically for 3.0 m (10 ft) or more, with or without concrete encasement. The phrase 'effectively grounded' does not appear in this section and is not the specified condition.

NEC NEC 250.53(A)(3)Question 2

Per NEC 250.53(A)(2) Exception, a single rod electrode that does not have a resistance to earth of 25 ohms or less shall be supplemented by an additional electrode. Per 250.53(A)(3), what is the minimum spacing between the two rod electrodes?

  • A3 feet
  • B6 feet
  • C8 feet
  • D10 feet
Show explanation

NEC 250.53(A)(2) requires a single rod, pipe, or plate electrode to be supplemented by an additional electrode unless it has a resistance to earth of 25 ohms or less. Per 250.53(A)(3), where multiple rod, pipe, or plate electrodes are installed to meet this requirement, they shall be not less than 1.8 m (6 ft) apart.

NEC NEC 250.119Question 3

Per NEC 250.119, equipment grounding conductors may be identified by which of the following methods?

  • AContinuous green color or green with yellow stripes
  • BWhite or gray insulation
  • CBlue insulation
  • DRed insulation
Show explanation

NEC 250.119 requires EGCs to be identified by continuous green insulation, green with one or more yellow stripes, or bare copper.

NEC NEC 250.64(A)Question 4

Per NEC 250.64(A), a grounding electrode conductor made of aluminum or copper-clad aluminum shall not be installed in which location?

  • AInside rigid metal conduit
  • BIn direct contact with masonry or the earth, or where subject to corrosive conditions
  • CIn PVC conduit
  • DInside EMT
Show explanation

NEC 250.64(A) prohibits aluminum or copper-clad aluminum grounding electrode conductors from being installed where in direct contact with masonry, the earth, or subject to corrosive conditions.

NEC NEC Table 250.122Question 5

Per NEC Table 250.122, what is the minimum size copper equipment grounding conductor required for a branch circuit protected by a 60-ampere overcurrent device?

  • A12 AWG
  • B10 AWG
  • C8 AWG
  • D6 AWG
Show explanation

Per NEC Table 250.122, a branch circuit protected by a 60 A overcurrent device requires a minimum 10 AWG copper equipment grounding conductor. The EGC is sized based on the rating of the overcurrent device, not the size of the phase conductors.

Practice all 5 grounding & bonding questions

7-day free trial. Full explanations, timed exams, progress tracking.

Start Free Trial