Electrician Prep

Practice Questions: Box Fill

Real questions from our bank, all referenced to NEC 2026. Tap “Show explanation” after you answer.

NEC NEC 314.16(B)Question 1

You are installing a 4" × 2-1/8" deep device box. The box contains three 12 AWG conductors, two 12 AWG equipment grounding conductors, one internal cable clamp, and one single-gang device (yoke). Per NEC 314.16, how many cubic inches of volume is required?

  • A13.50 cubic inches
  • B15.75 cubic inches
  • C18.00 cubic inches
  • D20.25 cubic inches
Show explanation

Per NEC Table 314.16(B), 12 AWG = 2.25 cu in each. Box fill: 3 conductors (3 × 2.25 = 6.75) + 1 EGC count (1 × 2.25 = 2.25) + 1 clamp count (1 × 2.25 = 2.25) + 1 device/yoke (2 × 2.25 = 4.50) = 15.75 cu in. Note: Per 314.16(B)(4), each device or equipment yoke counts as 2 conductor volumes.

NEC NEC Table 314.16(B)Question 2

How much volume must be allotted for each 12 AWG conductor in an outlet box, per NEC Table 314.16(B)?

  • A2.00 cubic inches
  • B2.25 cubic inches
  • C2.50 cubic inches
  • D3.00 cubic inches
Show explanation

Per NEC Table 314.16(B), each 12 AWG conductor is allotted 2.25 cubic inches of free volume. The free-volume requirements are additive for every conductor counted in the box.

NEC NEC 314.16(B)(2)Question 3

An outlet box contains one or more internal cable clamps. Per NEC 314.16(B)(2), how are the clamps counted in the box fill calculation?

  • AOne conductor volume allowance, based on the smallest conductor in the box
  • BOne conductor volume allowance, based on the largest conductor in the box
  • CTwo conductor volume allowances, based on the largest conductor in the box
  • DThey are not counted in the box fill calculation
Show explanation

Per NEC 314.16(B)(2), where one or more internal cable clamps are present in the box, a single volume allowance in accordance with Table 314.16(B) is required, based on the largest conductor present in the box.

NEC NEC 314.16(B)(3)Question 4

A box contains one fixture stud and one hickey. How many conductor volume allowances must be added for these fittings per NEC 314.16(B)(3)?

  • A1 allowance
  • B2 allowances
  • C3 allowances
  • D0 allowances — support fittings are exempt
Show explanation

Per NEC 314.16(B)(3), each fixture stud or hickey in a box counts as a single conductor volume allowance based on the largest conductor present. Two fittings require two allowances.

NEC NEC 314.16(B)(4)Question 5

A device box contains one duplex receptacle mounted on a single yoke. How many conductor volume allowances must be added for the device per NEC 314.16(B)(4)?

  • AOne, based on the largest conductor connected to the device
  • BTwo, based on the largest conductor connected to the device
  • CTwo, based on the smallest conductor connected to the device
  • DZero — devices are not counted
Show explanation

Per NEC 314.16(B)(4), each yoke or strap containing one or more devices or equipment requires a double volume allowance, sized based on the largest conductor connected to any device on that yoke.

Practice all 5 box fill questions

7-day free trial. Full explanations, timed exams, progress tracking.

Start Free Trial