Practice Questions: Raceway Sizing

Real questions from our bank, all referenced to NEC 2026. Tap “Show explanation” after you answer.

NEC NEC Chapter 9, Table 1Question 1

Per NEC Chapter 9 Table 1, when installing 3 or more conductors in a single conduit, the maximum conduit fill percentage allowed is:

  • A31%
  • B40%
  • C53%
  • D60%
Show explanation

NEC Chapter 9, Table 1 specifies 40% fill for 3 or more conductors. One conductor = 53%, two = 31%, three+ = 40%.

NEC NEC Chapter 9, Tables 1, 4, and 5Question 2

You need to install four 12 AWG THHN conductors in EMT. Per NEC Chapter 9 Table 5, each 12 AWG THHN conductor has an area of 0.0133 sq in. What is the minimum trade size EMT required? (1/2" EMT at 40% = 0.122 sq in; 3/4" EMT at 40% = 0.213 sq in)

  • A1/2 inch
  • B3/4 inch
  • C1 inch
  • D1-1/4 inch
Show explanation

Total conductor area = 4 × 0.0133 sq in = 0.0532 sq in. Per NEC Chapter 9 Table 4, 1/2" EMT has an internal area of 0.304 sq in; at 40% fill (Table 1, three or more conductors) the allowable fill is 0.122 sq in, which exceeds the required 0.0532 sq in. Therefore 1/2" EMT is the minimum trade size required. 3/4" EMT is not needed.

NEC NEC 300.17 and Chapter 9, Table 1Question 3

How many 12 AWG THHN conductors can be installed in a 3/4" EMT conduit?

  • A12 conductors
  • B16 conductors
  • C18 conductors
  • D20 conductors
Show explanation

Per NEC Chapter 9, Table 1, the fill for 3 or more conductors is limited to 40%. From NEC Chapter 9, Table 4, the 40%-fill area of 3/4" EMT = 0.213 sq in. From NEC Chapter 9, Table 5, each 12 AWG THHN conductor = 0.0133 sq in. Maximum conductors = floor(0.213 / 0.0133) = floor(16.0) = 16. This is confirmed by NEC Annex C, Table C.1 (16 conductors of 12 AWG THHN in 3/4" EMT). Correct answer: 16 conductors.

NEC NEC Chapter 9, Tables 1 and 4Question 4

What is the minimum EMT conduit size required for 10 conductors of 14 AWG THHN?

  • A1/2" EMT
  • B3/4" EMT
  • C1" EMT
  • D1-1/4" EMT
Show explanation

Per NEC Chapter 9, Table 1, the fill for 3 or more conductors is limited to 40%. Total conductor area = 10 × 0.0097 sq in (14 AWG THHN, per Table 5) = 0.097 sq in. From NEC Chapter 9, Table 4, the 40%-fill area of 3/4" EMT = 0.213 sq in. 0.097 sq in < 0.213 sq in — 3/4" EMT is sufficient. This is confirmed by NEC Annex C, Table C.1: 3/4" EMT accommodates up to 22 conductors of 14 AWG THHN, which exceeds the 10 required. Correct minimum conduit size: 3/4" EMT.

NEC NEC Chapter 9, Tables 1 and 4Question 5

How many 10 AWG THHN conductors fit in a 1-1/4" EMT conduit at 40% fill?

  • A16 conductors
  • B20 conductors
  • C24 conductors
  • D28 conductors
Show explanation

Per NEC Chapter 9, Table 1, the fill for 3 or more conductors is limited to 40%. From NEC Chapter 9, Table 4, the 40%-fill area of 1-1/4" EMT = 0.598 sq in. From NEC Chapter 9, Table 5, each 10 AWG THHN = 0.0211 sq in. Maximum conductors = floor(0.598 / 0.0211) = floor(28.34) = 28. This is confirmed by NEC Annex C, Table C.1 (28 conductors of 10 AWG THHN in 1-1/4" EMT). Correct answer: 28 conductors.

Practice all 24 raceway sizing questions